External equipments selection table

Print

User Rating: 5 / 5

Star ActiveStar ActiveStar ActiveStar ActiveStar Active
 

There are many connection (cable, busbar etc) and protection (circuit breaker, HV fuse etc) equipments have been user externally on the transformers.

Rated Power (kVA) HV Side  LV Side
 In (Amp) HV Fuse (Amp) In (Amp)    MCB* (Amp)    Transformer- Distribution Panel Connection   
 30 kV 15 kV  10 kV 30 kV 15 kV 10 kV  Cable (mm2 Busbar Size (mm)  
CU AL
50 0,96 1,92 2,75 6 6 6 72,17 3 x 100 3 x 25 + 16 30 x 3 40x 5
100 1,92 3,85 5,5 6 10 16 144,34 3 x 160 3 x 50 + 25 40 x 3 40 x 5
160 3,08 6,16 8,8 10 16 25 230,94 3 x 250 3 x 95 + 50 40 x 3 40 x 5
250 4,81 9,62 13,75 10 20 30 360,84 3 x 400 3 x 150 + 70 40 x 3 40 x 5
400 7,7 15,4 21,99 16 30 40 577,35 3 x 630 2 ( 3 x 150) 40 x 5 50 x 5
500 09,62 19,25 27,49 20 50 63 721,69 3 x 800 -- 40 x 10 50 x 10
630 12,12 24,25 34,64 30 50 63 909,33 3 x 1000 -- 50 x 10 60 x 10
800 15,4 30,79 43,99 30 63 80 1154,7 3 x 1400 -- 60 x 10 80 x 10
1000 19,25 38,49 54,99 40 80 100 1443,38 3 x 1600 -- 80 x 10 100 x 10
1250 24,06 48,11 68,73 50 100 125 1804,22 3 x 2150 -- 100 x 10 2(80 x 10)
1600 30,79 61,58 87,98 63 125 160 2309,4 3 x 2500 -- 2(80 x 10) 2(100 x 10)
2000 38,49 76,98 109,97 63 125 160 2886,75 3 x 3200 -- 2(100 x 10) 2(100 x 15)

* MCB : Moulded case circuit breaker

** Technical information given above is only for informative purposes.