Dissolved Gas Analysis (DGA) – Interpreting Transformer Oil Test Results

There is no translation available.

Every fault inside an oil-filled transformer leaves a chemical signature. Localised heating, partial discharge and arcing each break down mineral oil and cellulose insulation in a different way, releasing a characteristic mixture of gases that dissolves in the oil. Dissolved gas analysis reads that mixture and identifies what is happening inside a sealed tank without opening it.

It is the single most informative diagnostic test available for a transformer in service, and the earliest warning of a developing fault.

The Key Gases

Gas Formula What Its Presence Indicates
Fault Gases
Hydrogen H₂ Produced by every fault type. High H₂ with little else points to partial discharge.
Methane CH₄ Low-temperature thermal decomposition of oil, typically below 300 °C.
Ethane C₂H₆ Thermal faults in the 150–300 °C range.
Ethylene C₂H₄ Higher-temperature thermal faults, above roughly 300 °C.
Acetylene C₂H₂ Arcing. Requires temperatures above 700 °C — its presence is always significant.
Cellulose Degradation
Carbon monoxide CO Paper insulation overheating or ageing.
Carbon dioxide CO₂ Normal paper ageing; a rising CO₂/CO ratio suggests thermal degradation of cellulose.
Non-Fault Gases
Oxygen O₂ Ingress of air. In a sealed unit, indicates a leak.
Nitrogen N₂ Normal in nitrogen-blanketed units; otherwise indicates air ingress.
Acetylene is the gas to watch. It requires arc temperatures to form. Any measurable C₂H₂ in a transformer that has not experienced a through fault warrants investigation, regardless of how low the absolute concentration appears.

Typical Concentration Limits

IEC 60599 gives ranges of gas concentrations observed in transformers without known faults. Values above the 90th percentile are considered abnormal and warrant closer monitoring.

Gas Typical Range (ppm) Investigate Above (ppm)
Hydrogen (H₂) 50 – 150 150
Methane (CH₄) 30 – 130 130
Ethane (C₂H₆) 20 – 90 90
Ethylene (C₂H₄) 60 – 280 280
Acetylene (C₂H₂) 2 – 20 20
Carbon monoxide (CO) 400 – 600 600
Carbon dioxide (CO₂) 3800 – 14000 14000
Ranges vary by design and duty. These figures apply to transformers without on-load tap changers communicating with the main tank. Units with OLTCs, sealed units and free-breathing units all have different baselines. The most reliable reference is the transformer's own history.

Rate of Change Matters More Than Absolute Value

A transformer that has operated for twenty years with 120 ppm of hydrogen is behaving normally. The same transformer showing 120 ppm after a sample taken three months earlier showed 30 ppm is telling you something has changed.

The rate of gas generation is the more useful indicator:

  • Below 10 % increase per month — normal ageing, continue routine sampling
  • 10 to 30 % per month — increase sampling frequency, begin trending
  • Above 30 % per month — active fault, investigate without delay

This is why a single DGA result has limited value. The test becomes diagnostic when there is a history to compare against.

The Duval Triangle

The Duval Triangle plots three gases — methane, ethylene and acetylene — as relative percentages of their sum, and reads the fault type from which zone the point falls into. It is the most widely used graphical interpretation method and is referenced in IEC 60599.

D1 D2 DT T3 T2 T1 PD 100 % CH₄ 100 % C₂H₂ 100 % C₂H₄ % CH₄ % C₂H₄ % C₂H₂ PD — partial discharge D1 — low energy discharge D2 — high energy discharge DT — mixed thermal and electrical
Duval Triangle 1 for mineral oil. Thermal zones: T1 below 300 °C, T2 between 300 and 700 °C, T3 above 700 °C.

How to Plot a Point

Take the concentrations of the three gases in ppm and express each as a percentage of their sum:

%CH₄ = 100 × CH₄ / (CH₄ + C₂H₄ + C₂H₂)
and similarly for %C₂H₄ and %C₂H₂

Worked Example

A DGA report returns CH₄ = 90 ppm, C₂H₄ = 250 ppm, C₂H₂ = 5 ppm.

Sum = 90 + 250 + 5 = 345 ppm

%CH₄ = 100 × 90 / 345 = 26 %

%C₂H₄ = 100 × 250 / 345 = 72 %

%C₂H₂ = 100 × 5 / 345 = 2 %

This point falls in zone T3 — a thermal fault above 700 °C.

The high ethylene with very little acetylene is the signature of severe overheating without arcing. Likely causes include a bad joint in the winding circuit, a circulating current in the core or tank, or a blocked oil duct producing a local hotspot.

Fault Types and What They Mean

Zone Fault Type Typical Cause and Severity
PD Partial discharge Corona in gas bubbles or voids in the insulation. Slow degradation; monitor and investigate moisture content and oil condition.
D1 Discharge of low energy Sparking or tracking across insulation surfaces. Carbonised paths may be present. Requires investigation.
D2 Discharge of high energy Arcing with power follow-through. Metal fusion and extensive carbonisation likely. Serious — remove from service for inspection.
T1 Thermal fault below 300 °C Overloading, restricted oil flow or an insulated conductor running hot. Paper may be discoloured but not carbonised.
T2 Thermal fault 300–700 °C Localised hotspot in the winding or a defective connection. Paper carbonisation begins in this range.
T3 Thermal fault above 700 °C Severe overheating — bad contact, circulating current in the core or tank, or a shorted lamination. Requires prompt investigation.
DT Mixed thermal and electrical Combination of mechanisms, or a fault evolving from one type to another. Trend over successive samples to clarify.

Limitations of the Method

The Duval Triangle always returns a diagnosis, whether or not a fault exists. Because there is no "normal" zone, a healthy transformer with trace levels of all three gases will still plot somewhere on the triangle.

This produces the most common misuse of the method: applying it to a unit whose absolute gas concentrations are well within normal limits, and then acting on a diagnosis that has no physical basis.

Correct sequence: first confirm that gas concentrations exceed typical values or are rising abnormally. Only then use the Duval Triangle to identify what kind of fault is producing them.

Other limitations worth knowing:

  • The triangle identifies fault type, not location. A T3 result does not distinguish between a winding hotspot and a circulating current in the tank.
  • Two simultaneous faults produce a point somewhere between their individual signatures, which may fall in a zone corresponding to neither.
  • Zone boundaries differ for alternative fluids. Natural and synthetic esters require the adjusted boundaries of Duval Triangle 3.
  • Units where on-load tap changer oil communicates with the main tank show elevated acetylene from normal switching operations, not from a fault.

Sampling Practice

Poor sampling invalidates the analysis. The gases of interest are dissolved in the oil and will escape if the sample is exposed to air.

  • Use a gas-tight syringe or an approved sealed container, never an open bottle
  • Flush the sampling valve before drawing the sample to clear stagnant oil from the pipework
  • Take the sample with the transformer in normal service and at stable temperature, not immediately after energisation
  • Exclude all air bubbles from the syringe — a visible bubble can significantly alter the reading
  • Record the oil and ambient temperature, and the transformer loading at the time of sampling
  • Deliver to the laboratory promptly and keep the sample out of direct sunlight

Recommended Sampling Intervals

Situation Interval
New unit, first year After commissioning, then at 6 and 12 months
Routine service, gas levels normal Annually
Critical or unmanned installation Every 6 months, or continuous online monitoring
Gas levels elevated but stable Every 3 months
Gas levels rising Monthly or more frequently until the trend is understood
After a through fault or protection operation Immediately, then again after 24 hours

Practical Notes

  • Establish a baseline. The first DGA on a new transformer is the reference against which every later sample is judged.
  • Use the same laboratory throughout. Inter-laboratory variation on the same sample can exceed the changes you are trying to detect.
  • A sudden appearance of acetylene after a system fault may reflect that fault rather than an internal defect. Sample again after the unit has run normally for a period.
  • Read DGA alongside the other oil tests — moisture content, dielectric strength, acidity and interfacial tension. Gases indicate what is happening; the physical tests indicate how much life the insulation has left.
  • Thermal faults identified as T1 or T2 can often be correlated with the insulation thermal class and observed temperature rise. See Transformer Insulation Thermal Classes and Temperature Limits.
Note: Concentration limits and interpretation guidance in this article follow IEC 60599 for mineral oil transformers. Individual utility standards and manufacturer recommendations may specify different thresholds. Diagnosis of a suspected fault should be confirmed by a qualified engineer with access to the unit's full service history.

Replacing a transformer that has reached end of life?

DATSAN manufactures oil-immersed distribution and power transformers from 25 kVA to 30 MVA, built to IEC 60076 with routine and special testing to ISO/IEC 17025. Browse the full product range or contact our engineering team to discuss a like-for-like replacement.

Transformer Manufacturer

DATSAN Transformer manufactures oil-immersed distribution and power transformers for industrial, utility, and infrastructure projects worldwide.

Established in 1992, DATSAN combines over 30 years of engineering experience with modern manufacturing and testing capabilities. Our products are designed in accordance with IEC 60076, ANSI C57 and relevant international standards, with Ecodesign-compliant options available upon request.

Contact Us

Datsan Elk. İnş. San. ve Tic. Ltd. Şti.

Address: Kızıltepe Mardin Karayolu 6.km
Kızıltepe, 47400 Mardin / TÜRKİYE

Phone : +90 (482) 215 3188
Fax : +90 (482) 215 1199