Transformer Impedance Voltage (%Uk) – What It Means and How to Choose

There is no translation available.

Impedance voltage is one of the few transformer parameters that a purchaser genuinely chooses rather than accepts. It appears on the rating plate as a percentage, and that single number determines the fault current the installation must withstand, how much the output voltage sags under load, and whether the unit can be paralleled with an existing one.

It is also the parameter most often specified by copying a previous project without asking whether the value still fits.

The Definition

Impedance voltage is the voltage that must be applied to one winding, with the other short-circuited, to drive rated current through the transformer. It is expressed as a percentage of rated voltage.

Uk% = 100 × Usc / Un
Usc = applied voltage producing rated current with the secondary shorted  •  Un = rated voltage

A transformer with 4 % impedance requires 4 % of rated voltage — 16 V on a 400 V winding — to circulate full rated current when the other side is short-circuited. This is measured directly as a routine test on every unit.

Where It Comes From

Impedance is not a component added to the transformer. It is the combined effect of two things inherent in the construction:

  • Winding resistance — the resistive component, responsible for load losses. Small in comparison to the reactive part in most designs.
  • Leakage reactance — the dominant component. Arises from magnetic flux that links one winding but not the other, determined mainly by the physical separation between HV and LV windings and by the winding geometry.

Because leakage reactance depends on geometry, impedance is set at the design stage by how the windings are arranged. A designer increases impedance by moving the windings further apart or changing their proportions — which also increases size, material and cost.

This is why non-standard impedance costs more. It is not a surcharge for special handling; the transformer is physically different.

Standard Values

IEC 60076-5 and EN 50588-1 establish standard impedance values for distribution transformers:

Rated Power Standard Uk%
25 – 630 kVA 4 %
631 – 2500 kVA 6 %
2500 kVA and above 6 – 10 %, design dependent
Power transformers, transmission level 10 – 20 %
Tolerance: IEC 60076-1 permits ±10 % on the guaranteed impedance value for two-winding transformers. A unit specified at 6 % may measure anywhere between 5.4 % and 6.6 % and still comply.

Effect on Fault Level

This is the consequence that most often governs the choice. Short-circuit current at the transformer terminals is inversely proportional to impedance:

Isc = In × 100 / Uk%
Impedance Multiple of Rated Current Fault Current, 1000 kVA at 400 V
4 % 25 × 36.1 kA
5 % 20 × 28.9 kA
6 % 16.7 × 24.1 kA
8 % 12.5 × 18.0 kA
10 % 10 × 14.4 kA
The full method, including the upstream network contribution and peak asymmetrical current, is covered in Transformer Short-Circuit Current Calculation.

The switchgear implication is direct. Moving from 4 % to 6 % on a 1000 kVA unit reduces the fault level from 36 kA to 24 kA — which can be the difference between a standard LV panel and a considerably more expensive one.

Effect on Voltage Regulation

Higher impedance means a larger voltage drop between no load and full load. The approximate regulation is:

Regulation ≈ UR% × cos φ + UX% × sin φ
UR = resistive component  •  UX = reactive component  •  φ = load power factor angle

For practical purposes, regulation at full load approaches the impedance percentage when the load power factor is low, and is considerably less at unity power factor.

Impedance Regulation at PF 1.0 Regulation at PF 0.8
4 % ~1.2 % ~3.2 %
6 % ~1.5 % ~4.4 %
10 % ~2.0 % ~7.0 %
Values are indicative and depend on the ratio of resistive to reactive components in the specific design.

Where voltage stability at the load matters — sensitive electronics, long feeders already carrying voltage drop, installations near the lower limit of the permitted supply range — lower impedance is preferable.

Effect on Motor Starting

Direct-on-line motor starting draws six to eight times full load current for a few seconds. That inrush passes through the transformer impedance and produces a voltage dip across the whole installation.

Where a large motor starts against a relatively small transformer, this dip can be severe enough to drop out contactors, trip undervoltage protection, or stall the motor itself. In such installations the impedance selection may be governed by motor starting rather than by fault level.

Effect on Parallel Operation

Transformers in parallel share load in inverse proportion to their impedances. Two units of the same rating but different impedance will not share equally — the one with lower impedance takes more.

IEC guidance is that paralleled transformers should have impedances within 10 % of each other. Beyond that, one unit reaches its rating while the other still has spare capacity, and the total usable output is less than the sum of the ratings. The calculation and worked examples are in Parallel Operation of Transformers.

Watch the tolerance band. Two transformers both specified at 6 % can measure 5.4 % and 6.6 % and both comply with the standard — a 22 % difference between them. Where parallel operation is planned, request the measured impedance from each test report rather than relying on the nameplate value.

Effect on Losses and Cost

Higher impedance requires greater separation between windings, which means a larger core window, more core material, longer mean turn length and more conductor.

Aspect Lower Impedance Higher Impedance
Fault current Higher Lower
Switchgear rating required Higher, more expensive Lower, less expensive
Voltage regulation Better Worse
Motor starting voltage dip Smaller Larger
Reactive power consumption Lower Higher
Transformer size and cost Lower Higher
Short-circuit mechanical stress Higher Lower

The trade-off is genuine and there is no universally correct answer. What matters is that the choice is made deliberately rather than inherited from a previous specification.

When to Depart from the Standard Value

Specify higher impedance where:

  • Calculated fault level exceeds the rating of existing or preferred switchgear
  • Several transformers will operate in parallel and the combined fault level is the constraint
  • The installation is close to a strong network with a high upstream fault level
  • Existing switchgear is being retained in a retrofit

Specify lower impedance where:

  • Voltage regulation at the load is critical
  • Large motors start direct-on-line against a modest transformer rating
  • The supply voltage is already near the lower end of the permitted range
  • Reactive power consumption is penalised by the tariff

Match an existing value where:

  • The new unit will be paralleled with an installed transformer
  • A utility standard or project specification states the required value
  • The transformer is a like-for-like replacement in an installation whose protection settings are already established

Practical Notes

  • Impedance is measured on the principal tap. On a transformer with a wide tap range the value at the extreme taps differs, and the test report should state the values across the range where this matters.
  • The percentage refers to the transformer's own rated power. A 6 % impedance on a 630 kVA unit and a 6 % impedance on a 1600 kVA unit are different absolute impedances entirely.
  • Where the specification does not state an impedance, the manufacturer supplies the standard value for that rating. If a particular figure is needed, it must appear in the enquiry — changing it after the design is fixed means redesigning the transformer.
  • Protection coordination studies should use the measured value from the test report, not the nominal specification, once the unit is delivered.
Note: Regulation figures in this article are approximate and assume typical ratios of resistive to reactive impedance components. Values for a specific transformer are calculated from the resistance and reactance stated in its test report.

Need a specific impedance value?

DATSAN manufactures oil-immersed transformers to customer-specified impedance voltage in accordance with IEC 60076, with the measured value confirmed in the test report. Browse the full product range or contact our engineering team with your protection coordination requirements.

Transformer Manufacturer

DATSAN Transformer manufactures oil-immersed distribution and power transformers for industrial, utility, and infrastructure projects worldwide.

Established in 1992, DATSAN combines over 30 years of engineering experience with modern manufacturing and testing capabilities. Our products are designed in accordance with IEC 60076, ANSI C57 and relevant international standards, with Ecodesign-compliant options available upon request.

Contact Us

Datsan Elk. İnş. San. ve Tic. Ltd. Şti.

Address: Kızıltepe Mardin Karayolu 6.km
Kızıltepe, 47400 Mardin / TÜRKİYE

Phone : +90 (482) 215 3188
Fax : +90 (482) 215 1199