Short-circuit current determines the breaking capacity required from downstream switchgear, the mechanical bracing needed in busbar systems, and the withstand rating of every component between the transformer and the fault. It is set almost entirely by one parameter on the rating plate: the impedance voltage.
The Formula
For a fault at the transformer terminals, assuming an infinite upstream source:
Full load current is obtained from the rated power and voltage — see Transformer Full Load Current Calculation for the method and reference tables.
The relationship is inverse: halving the impedance doubles the fault current. A transformer with 4 % impedance delivers 25 times its rated current into a terminal fault; at 6 % impedance the figure drops to about 16.7 times.
Worked Example
A 630 kVA transformer, 400 V secondary, 4 % impedance voltage:
Step 1 — full load current:
In = 630,000 / (1.732 × 400) = 909 A
Step 2 — short-circuit current:
Isc = 909 × 100 / 4
Isc = 22,725 A ≈ 22.7 kA
The same unit built to 6 % impedance would produce approximately 15.2 kA — a difference that can change the required switchgear rating and therefore the cost of the whole LV installation.
Standard Impedance Values
Impedance voltage is not arbitrary. IEC 60076-5 and EN 50588-1 establish standard values for distribution transformers:
Short-Circuit Current Table — 400 V Secondary
The Infinite Bus Assumption
The formula above assumes the upstream network is an infinite source — that is, the HV supply itself contributes no impedance. In practice the network has a finite fault level, and the actual short-circuit current at the transformer terminals is slightly lower than calculated.
Where the upstream fault level is known, the combined result is:
For most distribution installations the network contribution is large enough that ignoring it introduces an error of only a few percent — and the error is on the conservative side, since the calculated value is higher than reality. For installations close to a generation source or a strong substation, the full calculation should be carried out.
Peak Asymmetrical Current
The values above are RMS symmetrical currents. During the first cycle after fault inception, the current contains a DC offset component that raises the instantaneous peak considerably. IEC 60909 defines a peak factor that depends on the X/R ratio of the circuit:
- For typical distribution transformers, the peak factor is in the range of 1.8 to 2.2
- A 22.7 kA symmetrical fault can therefore reach an instantaneous peak of approximately 50 kA
- Busbar mechanical bracing and switchgear making capacity must be rated against this peak, not the RMS value
Practical Implications
- Switchgear selection — the breaking capacity of LV circuit breakers must exceed the calculated fault current at their point of installation. Cable impedance reduces the fault level with distance from the transformer.
- Impedance as a design choice — higher impedance limits fault current and reduces switchgear cost, but increases voltage regulation and reactive power consumption. The trade-off should be evaluated at the design stage.
- Parallel operation — two transformers operating in parallel roughly double the available fault current at the common busbar. Switchgear must be rated for the combined figure.
- Withstand duration — IEC 60076-5 requires transformers to withstand a terminal short circuit for 2 seconds without damage. This is a thermal and mechanical requirement verified by design calculation or type test.
Need a specific impedance value for your project?
DATSAN manufactures oil-immersed transformers with customer-specified impedance voltage in accordance with IEC 60076. Browse the full product range or contact our engineering team to discuss your protection coordination requirements.
English (English)
Turkish (Türkçe)
French (Français)
Arabic (عربي)